Where to place temperature sensors in a server room: ASHRAE guidance and how many you need

Where to place temperature sensors in a server room: ASHRAE guidance and how many you need

Temperature sensors belong at the air inlet of the IT equipment, on the front of the rack, because that is the temperature ASHRAE limits refer to. For a small server room that means one probe at the top front of each rack, or of every second rack in a row, plus one humidity sensor per room. A sensor on the wall, on the ceiling or next to the air conditioner measures the room, not the servers.

In short

  • ASHRAE limits (18–27 °C recommended) apply to the equipment inlet. Measure at the front of the rack, never at the exhaust or on the wall.
  • Full data-centre practice is three probes per rack (top, middle, bottom of the front). A small server room gets by with one at the top front of each rack.
  • Put one humidity sensor per room in the cold aisle, and one leak sensor under each cooling unit.
  • Add one probe at the return air of the AC unit. The inlet-to-return difference tells you whether cooling is keeping up before any limit is crossed.

Why the inlet is the only place that counts

Servers are specified by the temperature of the air they draw in. ASHRAE TC 9.9 defines its classes, A1 to A4, by inlet dry-bulb temperature, and a server's own thermal management is driven by its inlet sensor. The exhaust at the back is routinely 10–15 °C hotter and tells you how hard the server works, not whether it is safe.

A wall thermostat averages the whole room, cold aisle and hot aisle together, and reports a number nobody can act on. A probe hanging near the AC supply grille reports the coldest air in the room and hides the hot spot two racks away. The only reading that maps directly onto the ASHRAE envelope and the manufacturer's warranty is the one taken a few centimetres in front of the equipment intake.

Sensors in the rack: three, one, or none

Data-centre practice, following ASHRAE TC 9.9 guidance, is three probes on the front of each rack at the top, middle and bottom, aligned with server inlets, to capture the vertical gradient. In a contained cold aisle the gradient is small and the three readings agree. In an ordinary server room with no containment the top probe can be 5–8 °C warmer than the bottom, because warm exhaust loops over the top of the rack and is drawn back in.

For a room of one to six racks a reduced scheme works: one probe at the top front of each rack, since that is always the warmest inlet, and one at the bottom of the rack that holds the UPS. If racks are identical and adjacent, every second rack is acceptable. A logger with up to four inputs such as EnviSensor ETH PoE covers two racks with two probes each, or one rack with top, bottom, door contact and leak sensor.

Rack sensor schemes
Scheme Probes per rack When
Full (ASHRAE practice) 3: top, middle, bottom of front Data centres, high-density racks, warranty claims
Reduced 1 at top front, plus 1 at UPS Server rooms of 1–6 racks
Row 1 at top front of every second rack Identical, adjacent racks in a row

Sensors in the room: humidity, return air, leaks

Humidity changes slowly and evenly across a room, so one sensor per room is enough, placed in the cold aisle at rack-inlet height. Humidity readings are temperature-dependent; a sensor placed in the hot exhaust reports a relative humidity that is meaningless for the inlet. ASHRAE's recommended range is roughly 40–60 % RH with a dew point ceiling; the low side matters for static discharge, the high side for condensation on cold surfaces.

Return air at the AC unit's intake is the second most useful temperature in the room. The difference between the rack inlet and the return air is the heat the cooling is removing. If the return climbs while the inlet is still fine, the unit is losing the race and you have hours of warning instead of minutes.

Leak sensors go on the floor under every cooling unit's drip tray, under the raised floor at its lowest point, and near any water pipe passing through or above the room. A point sensor costs about the same as a probe, so several are affordable.

How many sensors for a room of a given size

Starting point by room size
Room Temperature probes Humidity Leak Loggers
1 rack in a closet 2 (top inlet, UPS) 1 1 if plumbing nearby 1
2–4 racks, one AC unit 1 per rack + 1 return air 1 1 under AC + 1 floor 2
5–10 racks, two AC units 1 per rack top + 1 per AC return 1–2 1 per AC + 2 floor 3–5
Data hall, contained aisles 3 per rack (ASHRAE practice) 1 per aisle Perimeter tape + per unit DCIM-scale

The numbers scale with racks, not with square metres. An empty 40 m² room with two racks needs two loggers; the same room with ten racks needs five.

Five placements that give a false reading

  1. Next to the AC supply grille. Reports 16 °C all year and hides a 30 °C rack in the corner.
  2. On the back of the rack. Measures exhaust; will alarm at 35 °C while the inlet is a healthy 24.
  3. On the ceiling. Warmest air in the room, unrelated to any inlet. Useful only as a fire pre-warning, and a smoke detector does that better.
  4. Inside the logger's own housing. Built-in sensors read the electronics' self-heating. Use the external probe and place it where the air goes in.
  5. Behind the door of a closed cabinet, at the bottom. Coolest air in the cabinet. The switch at the top is 12 °C warmer.

Frequently asked questions

Where should a temperature sensor be placed in a server room?

At the air inlet of the IT equipment, on the front of the rack, ideally at the top where the inlet is warmest. Add one humidity sensor per room in the cold aisle and a probe at the AC return.

How many temperature sensors does a server room need?

One at the top front of each rack for a small room, three per rack (top, middle, bottom) in a data hall, plus one per air-conditioning return. A four-rack room typically has five to six probes on two loggers.

Should the sensor go at the front or the back of the rack?

The front. ASHRAE limits and server warranties refer to inlet temperature. The back measures exhaust, which is 10–15 °C hotter and not the number any limit refers to.

How many humidity sensors are needed?

One per room, or one per aisle in a data hall. Humidity changes slowly and evenly, so more sensors add little; placement in the cold aisle at inlet height is what matters.

Is a sensor on the wall good enough?

No. A wall sensor averages hot and cold air and misses the hot spot at the top of a rack. It can serve as a coarse room reading but not as the basis for alarms.

Related pages

Server room monitoring

Temperature, humidity, smoke and leaks: the limits and what to monitor first.

EnviSensTemp

Temperature probe for EnviSensor loggers, 1 / 3 / 5 m.

EnviSensLeak

Point leak sensor for under the AC and the raised floor.

Need monitoring at your site?

We will help you choose sensors and the way they run — locally on your LAN, in your own monitoring system or in the CE MonitorApp cloud.

Holder up
Szablon Shoper Modern 3.0™ od GrowCommerce
Shop is in view mode
View full version of the site
Sklep internetowy Shoper.pl